Power cables for stationary laying for 6-35 kV
1. Round-shaped, stranded, compacted current-carrying conductor:
- metarial:
АПвВнг-LS, АПвВнг, АПвКаВнг, АПвКаВнг-LS, АПвКсВнг, АПвКсВнг-LS – aluminum (А),
ПвВнг-LS, ПвВнг, ПвКаВнг, ПвКаВнг-LS ПвКсВнг, ПвКсВнг-LS – copper,
- section:
6 kV cables - 35-1000 sq. mm,
10, 15, 20, 35 kV cables – 50-1000 sq. mm;
2. Conductor screen made of extruded semiconducting cross-linked polyethylene;
3. Insulation made of cross-linked polyethylene (Пв);
4. Insulation screen made of extruded semiconducting cross-linked polyethylene;
5. Separating layer made of semiconducting tape;
6. Screen made of copper wires connected by means of copper tape:
- with section of minimum 16 sq. mm for cables with conductor section of 35-120 sq. mm,
- with section of minimum 25 sq. mm for cables with conductor section of 150-240 sq. mm,
- with section of minimum 35 sq. mm for cables with conductor section of over 300 sq. mm.
Note: Screen section is selected depending on short-circuit currents which shall be calculated according to field cable installation conditions. It is possible to manufacture cables with increased screen section.
7. Separating layer made of varnished glass tape;
8. Inner filling made of non-combustible PVC compound (for A category cables) and armored cables;
9. Separating layer made of varnished glass tape (for (A) category cables).
10. Armor made of aluminum wires (Ka) or aluminum alloy wires (Kc).
11. Sheath made of non-combustible PVC compound.
1. Round-shaped, stranded, compacted current-carrying conductor:
- metarial:
АПвПнг(В)-HF, АПвПнг(А)-HF – aluminum (А),
ПвПнг(В)-HF, ПвПнг(А)-HF – copper.
- section:
6 kV cables - 35-800 sq. mm,
10, 20, 35 kV cables – 50-800 sq. mm;
2. Conductor screen made of extruded semiconducting cross-linked polyethylene;
3. Insulation made of cross-linked polyethylene (Пв);
4. Insulation screen made of extruded semiconducting cross-linked polyethylene;
5. Separating layer made of semiconducting tape;
6. Screen made of copper wires connected by means of copper tape:
- with section of minimum 16 sq. mm for cables with conductor section of 35-120 sq. mm,
- with section of minimum 25 sq. mm for cables with conductor section of 150-240 sq. mm,
- with section of minimum 35 sq. mm for cables with conductor section of over 300 sq. mm.
Note: Screen section is selected depending on short-circuit currents which shall be calculated according to field cable installation conditions. It is possible to manufacture cables with increased screen section.
7. Separating layer made of varnished glass tape;
8. Inner sheath made of halogen-free polymer compound;
9. Thermal barrier made of varnished glass tapes;
10. Sheath made of halogen-free polymer compound.
Arrangement of halogen-free sheathed three-conductor cables which are flame-retardant if brunched.
1. Central filling made of low fire hazard PVC-bundle or copper wire in the center of sector cable core;
2. Round- or sector-shaped, stranded, compacted current-carrying conductor:
- metarial:
АПвПнг(В)-HF, АПвПнг(А)-HF, АПвБПнг(В)-HF, АПвБПнг(А)-HF – aluminum (А),
ПвПнг(В)-HF, ПвПнг(А)-HF, ПвБПнг(В)-HF, ПвБПнг(А)-HF – copper,
- section:
6 kW cables (round-shaped conductor) - 35-400 sq. mm,
10, 20, 35 kW cables (round-shaped conductor) – 50-400 sq. mm,
6, 10 kW cables (sector-shaped conductor) – 120–240 sq. mm;
3. Conductor screen made of extruded semiconducting cross-linked polyethylene;
4. Insulation made of cross-linked polyethylene (Пв);
5. Insulation screen made of extruded semiconducting cross-linked polyethylene;
6. Separating layer made of semiconducting crepe paper tape;
7. Screen made of copper wires connected by means of copper tape (for sector cables collective screen is applied over three insulated conductors):
- with section of minimum 16 sq. mm for cables with conductor section of 35-120 sq. mm,
- with section of minimum 25 sq. mm for cables with conductor section of 150-240 sq. mm,
- with section of minimum 35 sq. mm for cables with conductor section of over 300 sq. mm.
Note: Screen section is selected depending on short-circuit currents which shall be calculated according to field cable installation conditions. It is possible to manufacture cables with increased screen section.
8. Interphase filling made of halogen-free compound;
9. Armor made of steel galvanized tapes ;
10. Sheath made of halogen-free compound.