Cable arrangement elements.
1. Round-shaped, stranded, compacted current-carrying conductor:
- material:
АПвПнг(В)-HF, АПвПнг(А)-HF – aluminum (А),
ПвПнг(В)-HF, ПвПнг(А)-HF – copper.
- section:
6 kV cables - 25-800 sq. mm,
10, 20, 35 kV cables – 35-800 sq. mm;
2. Conductor screen made of extruded semiconducting cross-linked polyethylene;
3. Insulation made of cross-linked polyethylene (Пв);
4. Insulation screen made of extruded semiconducting cross-linked polyethylene;
5. Separating layer made of semiconducting tape;
6. Screen made of copper wires connected by means of copper tape:
- with section of minimum 16 sq. mm for cables with conductor section of 25-120 sq. mm,
- with section of minimum 25 sq. mm for cables with conductor section of 150-240 sq. mm,
- with section of minimum 35 sq. mm for cables with conductor section of over 300 sq. mm.
Note: Screen section is selected depending on short-circuit currents which shall be calculated according to field cable installation conditions. It is possible to manufacture cables with increased screen section.
7. Separating layer made of varnished glass tape;
8. Inner sheath made of halogen-free polymer compound;
9. Thermal barrier made of varnished glass tapes;
9. Armor made of steel galvanized wires;
10. Sheath made of halogen-free polymer compound.