NHXH E30/FE180, E90/FE180 0,66; 1kV
Power cables with copper conductors, insulated and sheathed by polymer composition, halogen-free, fire-resistant.
Construction:
1. Current-carrying conductor is made of copper, solid or stranded conductor, round- or sector-shaped, of class 1 or 2 as per GOST 22483.
2. Thermal barrier is a lapping made of two micaceous tapes.
3. Insulation is made of halogen-free polymer composition. Insulated conductors of multi-conductor cables have distinctive color. Insulation of neutral conductors is performed in blue color. Insulation of grounding conductors is performed in two colors (green and yellow).
4. Twist - insulated conductors of two-, three-, four- and five conductor cables are twisted. All conductors of the cable must be uniform. It is allowed to perform four conductor cables with one conductor of lesser section (grounding or neutral conductor).
5. Inner sheath is made of halogen-free polymer composition.
6. Outer sheath is made of halogen-free polymer composition.
Application:
– For power transmission and distribution in fixed plants for rated alternating voltage of 0.66 kV and 1 kV with frequency of up to 100 Hz.
– For industrial purposes and nuclear power stations (NPS) in NPS systems class 2.
– For installation in premises and cable structures, if there is no mechanical damage risk during operation.
– For electrical circuits which can operate in fire conditions.
Cables are designed for bunched installation.